Wire size · Chart
Service entrance wire size chart
For a 120/240-volt single-phase dwelling service, NEC Table 310.12 calls for 4/0 AWG aluminum or 2/0 AWG copper at 200 amps, 2 AWG aluminum or 4 AWG copper at 100 amps, and 600 kcmil aluminum or 400 kcmil copper at 400 amps. The table applies only when the conductors carry the entire load of the dwelling.
NEC Table 310.12 service conductor sizes
| Service rating | Copper | Aluminum |
|---|---|---|
| 100 A | 4 AWG | 2 AWG |
| 125 A | 2 AWG | 1/0 AWG |
| 150 A | 1 AWG | 2/0 AWG |
| 200 A | 2/0 AWG | 4/0 AWG |
| 225 A | 3/0 AWG | 250 kcmil |
| 300 A | 250 kcmil | 350 kcmil |
| 400 A | 400 kcmil | 600 kcmil |
Values for 120/240 V, 3-wire, single-phase dwelling services and main feeders. Long runs may need larger conductors for voltage drop.
What cable types are used from the transformer to the meter?
| Cable | Where it's used |
|---|---|
| URD (underground residential distribution) | Aluminum triplex for service laterals in conduit or direct burial |
| USE-2 | Single conductors for underground service entrance |
| SER / SEU | Service entrance cable on the building, meter to panel |
| THHN/THWN-2 in conduit | Individual conductors in a mast or riser |
How do you terminate aluminum service conductors?
- Strip without nicking the strands.
- Wire-brush the strands and apply antioxidant compound if the lug instructions call for it.
- Use lugs marked AL/CU.
- Torque to the manufacturer's value with a torque wrench or screwdriver (NEC 110.14(D)).
Related: underground service installation and meter base guide.
Frequently asked questions
What size aluminum wire is used for a 200 amp service?
4/0 AWG aluminum for the ungrounded (hot) conductors, per NEC Table 310.12 for single-phase dwelling services. Underground, this is commonly 4/0-4/0-2/0 aluminum URD cable, where the smaller conductor is the neutral.
Can I use copper instead of aluminum for a service?
Yes. A 200-amp service needs 2/0 AWG copper. Copper costs much more per foot, so aluminum is the standard for service laterals and service entrance cable. Both are safe when terminated on lugs rated for the conductor and torqued to specification.
Can the neutral be smaller than the hot conductors?
Often yes. The service neutral is sized for the calculated unbalanced load and grounding requirements, so a reduced neutral such as 2/0 aluminum with 4/0 hots is common on 200-amp services. Your electrician confirms the size.
Sources: NFPA 70 (NEC) Table 310.12, 110.14(D).