ElectricService101

Responsibility · Guide

Who owns the line from the transformer to the meter?

Updated November 20, 2026 · ElectricService101 Editorial Team · 5 min read

Quick answer

The utility owns the transformer and the meter. The homeowner owns the meter base and everything after it. Ownership of the service lateral in between varies: many utilities install and own the underground conductors while the customer digs the trench and supplies the conduit, and some cooperatives and municipal utilities make the customer own the lateral entirely. Your utility's service handbook defines the service point.

Where is the service point?

The service point is where the utility's equipment ends and yours begins. The NEC uses it to decide which rules apply: everything on the customer side falls under the electrical code and your inspector, and everything on the utility side falls under the utility's own standards. For an underground service it is often at the meter base terminals; for an overhead service it is usually the splice at the weatherhead.

Who supplies what? A typical split

ItemUtilityCustomer
Transformer and primary cableYes—
Trench to the transformerSometimesOften
Conduit, sweeps and riserSometimesOften
Service lateral conductorsOftenSometimes
Meter base—Yes
MeterYes—
Ground rods, clamps, grounding conductor—Yes

Example: AEP

AEP's 2026 Guide for Electric Service and Meter Installations has the customer provide the trench location, conduit, meter socket and grounding, while AEP provides the underground service lateral conductors to the service point. Its Ohio operating company requires 30 inches of cover, and the meter socket must be a listed ringless type centered 4 ft 6 in. to 5 ft 6 in. above grade.

What should you ask your utility before you start?

  • Where is the service point, and who owns the lateral conductors?
  • What conduit size, type and burial depth do you require, and do you want a pull string or mule tape?
  • Which meter bases are on your approved list?
  • Do you require an expansion fitting or slip joint on the riser?
  • What are the fees, and is any construction allowance credited?

Next: how to install an underground service lateral.

Frequently asked questions

Who pays to fix a damaged underground service line?

It depends on who owns it. If the utility owns the service lateral, it usually repairs it, though it may bill you for damage you caused. If your utility makes the customer own the lateral, the repair is yours and needs a licensed electrician. Call 811 before you dig to avoid damaging it in the first place.

Is the meter base the homeowner's responsibility?

Yes, in most utility territories. The utility owns the meter itself, but the meter base (socket), its mounting and the wiring beyond it belong to the property owner. A damaged or corroded meter base must be repaired by an electrician, and the utility pulls and resets the meter.

Sources: AEP, Guide for Electric Service and Meter Installations (rev. 1.05-2026); OPPD Meter Manual, Ch. 7 Underground Services (2026); Austin Energy, customer vs. utility equipment.